Emergency stop module with voltage failure detection BH 5903 The BH 5903, BL 5903 of the SAFEMASTER series enables automatic restarting of systems after a power failure. It is specially designed for applications that require immediate restarting when power is restored. Examples include compressor controls and water and wastewater technology. Advantages . E-stop with latching function . Automatic start when voltage returns after phase failure when no E-Stop was operated before phase failure . Cross fault monitoring . Short circuit and broken wire detection on all inputs Features . According to - Performance Level (PL) e and category 4 to EN ISO 13849-1 - SIL Claimed Level (SIL CL) 3 to IEC/EN 62061 - Safety Integrity Level (SIL 3) to IEC/EN 61508 . Reset after E-stop with push button . Output max. 3 NO contacts, see contacts . B_ 5903._ _ /00000: 1 E-stop loop 2-channel operated . B_ 5903._ _ /00020: 2 E-stop loops single channel operated . Feedback loop for external contact reinforcement . LED indication for channel 1 and 2 and for diagnostics . Removable terminal strips . Wire connection: also 2 x 1.5 mm2 stranded ferruled (isolated), DIN 46228-1/-2/-3/-4 or . 2 x 2.5 mm2 stranded ferruled DIN 46228-1/-2/-3 . BH 5903: width 45 mm BL 5903: width 90 mm Technical specifications Cat. / PL acc. to EN ISO 13849-1: 4/e 1- / 2-channel: 1, 2 Connection: Pluggable screw terminals Output contacts max.: 3 NO contacts Width: 45mm Cross fault detection: Yes SIL acc. to IEC/EN 62061: 3 Approvals: UL Nominal voltage: DC Thermal current Ith max.: 5A Type: BH 5903 Manufacturer: E. Dold & Söhne GmbH & Co. KG Type: BH5903.03/00000/61 DC24V Art. No.: 0053089