Insulation monitor
UH 5892
The insulation monitor UH 5892 of the series varimeter IMD monitors the ground resistance of isolated DC-voltage systems (IT-systems) with nominal voltage up to DC 600 V. The unit detects symmetrical as well as unsymmetrical faults. The separate auxiliary supply of AC/DC 24...60 V or AC/DC 85...230 V allows also monitoring when the system is without voltage. To indicate the actual ground resistance value the unit has an LED chain and an analogue output. When a fault is detected the relay switches and the red LED Alarm lights up, The device can be used for system with leakage capacities up to 20 uF.
| Auxiliary voltage: | AC/DC |
|---|---|
| Connection for indicator: | Yes |
| Earth fault indicator: | Yes |
| Enclosure design: | Switch cabinet |
| IMD type: | AC, AC/DC, DC |
| Nominal voltage IT system: | AC 0 - 400 V, DC 0 - 600 V |
| Response value: | 50 kΩ |
| Response value type: | Fixed |
| Type: | UH 5892 |
| Width: | 45 mm |
- Preventive fire and system protection
- Insulation monitoring of DC voltage systems up to 600 V nominal voltage
- No additional coupling device required
- Suitable for leakage capacitances up to 20 μF
- Monitoring also with voltage-free mains
- 2 wide voltage input ranges for auxiliary voltage
- Insulation monitoring according to IEC/EN 61557-8
- Detection of symmetric and asymmetric insulation faults
- 1 changeover contact for alarm
- Fixed response value RAN: 50 kΩ, other on request
- Internal reset and test pushbutton
- External test and reset pushbutton can be connected
- LED indicator for auxiliary voltage and alarm
- LED chain to indicate the current insulation resistance
- Automatic or manual reset, programmable
- Analogue output for insulating value
- External indicating instrument can be connected
- Closed circuit operation
- Open circuit operation on request
- With pluggable terminal blocks for easy exchange of devices
- with screw terminals
- or with cage clamp terminals - Width 45 mm