Frequency Relay MH 9837/5_0

MH9837_500.png

Features

• According to IEC / EN 60 255, VDE 0435 Teil 303
• Monitoring of AC voltage for under and overfrequency,
can be used also for pre-warning
• Separate relay outputs for over- or underfrequency
(1 or 2 changeover contacts each)
• Alternative usage for monitoring of a frequency window
• Separate adjustment of response value for over- or underfrequency
at 4 ranges each, 1.5 ... 200 Hz or 5 ... 600 Hz
• Second response value for prewarning possible
• Fast reaction time by measuring duration of cycle of input frequency
• Universal measuring input for AC-voltages of 15 ... 280 V
as well as 30 ... 550 V
• As option with measuring input for inverters
• Programmable hysteresis of response value: 2 ... 10 %
• Start up time delay programmable via terminals from
0 ... 50 s e.g. continuously
• Manual or auto-reset programmable via terminals
• Galvanic separation between measuring input, auxiliary voltage
and output contacts
• MH 9837/508: with galvanic separated analogue output (current/
voltage) and 11 step LED chain for the actual frequency
• MH 9837/5_0: with wide input range for auxiliary voltage available
(AC/DC 24 ... 60 V or AC/DC 110 ... 230 V)
• Closed circuit operation (de-energized on trip)
• LED indication for auxiliary voltage, measuring voltage and
alarm status
• Device available with 2 contacts
MK 9837N/5_0: 2 x 1 changeover contact
MH 9837/5_0: 2 x 2 changeover contacts or
wide auxiliary voltage range
• 2 possible compact designs:
MK 9837N/5_0: Width 22,5 mm
MH 9837/5_0: Width 45 mm

• According to IEC / EN 60 255, VDE 0435 Teil 303
• Monitoring of AC voltage for under and overfrequency,
can be used also for pre-warning
• Separate relay outputs for over- or underfrequency
(1 or 2 changeover contacts each)
•...

more...

Advantages / Customer benefit

• Separate output signals for under and over frequency
• Simple wiring
• Easy handling

Function Frequency Relay
1- / 3-phase 1
Standard measuring range 1,5 ... 600 Hz
Measuring range max. 600 Hz
Output contacts 2 x 2 w
Auxiliary voltage required +
Enclosure design Schaltschrank
Width 45 mm
Type MH 9837/5_0

Please select required language:

Datasheet / Operating Instructions, File: pdf, File size 337 KB

 

 

Your contact


    Competence on site

    Damit wir für Sie Ihren persönlichen Ansprechpartner finden können, geben Sie bitte die fünfstellige Postleitzahl Ihres Ortes in das Suchfeld ein.

    Contact for: