Product questions ?

+

Direct contact: 01245 324432

or send us a message.

Level Sensing Relay MK 9151N

MK9151N.png

Features

• According to IEC/EN 60 255, DIN VDE 0435-303
• 3 probe connections for 2-point and 1-point level control
• Also for use as moisture detector
• High interference resistance of the Measuring Circuit,
which is isolated from the mains
• Max. wire length to the probes: 1500 m
• Large setting range: 2 ... 450 kΩ
this permits differentiation between fluid and foam
• Separately adjustable response and release time delay
0.2 ... 20 s for MIN- and MAX-level
• Programmable for:
- 2 separate controllable output relays for MIN and MAX level
- common controlled output relays for 2-point hysteresis
level control
- open circuit operation
- closed circuit operation
• Measuring Circuit for probes works with internally generated
AC voltage (approx. 30 Hz), electrolytic behaviour does not
occur in the liquid
• For auxiliary voltages of 24 ... 415 V AC or 24 V DC
• LEDs for operation and state of contact
• 2 changeover relays with 1 changeover contact each
• IL 9151 and SL 9151 with safe separation according to
IEC/EN 61 140, IEC/EN 60 947-1
• Devices available in 3 enclosure versions:
IL 9151: depth 59 mm, with terminals at the bottom for
installation systems and industrial distribution
systems according to DIN 43 880
SL 9151,
MK 9151N: depth 98 mm, with terminals at the top for
cabinets with mounting plate and cable duct
• IL/SL 9151: 35 mm width
MK 9151N: 22.5 mm width

• According to IEC/EN 60 255, DIN VDE 0435-303
• 3 probe connections for 2-point and 1-point level control
• Also for use as moisture detector
• High interference resistance of the Measuring Circuit,
which is isolated from the mains
•...

more...
Function Level Sensing Relay
Measuring range max. 450 kΩ
Output contacts 2 x 1 w
Operate delay +
Enclosure design Installationsverteiler
Width 22,5 mm
Type MK 9151N