Features

• According to DIN EN 60255-1, DIN EN 60947-1
• Voltage and frequency monitoring for generator sets >30 kVA
on public grid, according to VDEW directive
• RP 9800: 3-phase voltage measurement to neutral
• Disconnection on rise and drop of voltage
• Disconnection on rise and drop of frequency
• Disconnection when 10 minute mean value differs to nominal voltage
(overvoltage)
• Frequency and voltage are indicated by separate output relays
• Permits connection or re-connection after adjustable time delay tw
• Protection against manipulation by sealable transparent cover
over setting switches
• Precise adjustment and indication of setting values according to the
directive
• High measuring accuracy
• Width 70 mm

• According to DIN EN 60255-1, DIN EN 60947-1
• Voltage and frequency monitoring for generator sets >30 kVA
on public grid, according to VDEW directive
• RP 9800: 3-phase voltage measurement to neutral
• Disconnection on rise and...

more...
Function Voltage and frequency monitor
1- / 3-phase 3
Standard measuring range 50 Hz; AC 230 V
Output contacts 2 w
Operate delay +
Enclosure design Installationsverteiler
Width 70 mm
Type RP 9800