Skip to main content Skip to search Skip to main navigation
Menu
Description

Undercurrent detection in single phase or 3-phase voltage systems.

Technical specifications
1- / 3-phase: 1
Auxiliary voltage: AC, AC/DC
Enclosure design: Distribution board
Measuring range: AC 0,1 - 50 A
Operate delay: Yes
Output contacts: 1 C/O contact, 2 C/O contacts
Type: IL 9271
Width: 35 mm
Features
  • According to IEC/EN 60255-1
  • IP 9271, SP 9271, SP 9271CT: 3-phase
    IK 9271, IL 9271, SK 9271, SL 9271, SL 9271CT: Single phase
  • Measuring ranges from AC 0.1 ... 100 A
  • IK 9271, SK 9271:
    With 4 ranges settable by rotational switch, 1 changeover contact
  • IL 9271, SL 9271:
    With 5 ranges settable by rotational switch, 1 changeover contact
    With 4 ranges programmable by bridges, 2 changeover contacts
  • IP 9271, SP 9271: with 1 range, 2 changeover contacts
  • Settable response value
  • Fixed hysteresis
  • Settable time delay
  • De-energized on trip
  • Optionally energized on trip
  • LED indicators
  • With auxiliary voltage
  • Auxiliary supply and measuring input galvanic separated
  • Devices available in 2 enclosure versions:
    - I-model, e.g. IK _ _ _ _, depth 61 mm with terminals at the bottom for installations systems and industrial distribution systems according to DIN 43 880
    - S-model, e.g. SK _ _ _ _, depth 100 mm with terminals at the top for cabinets with mounting plate and cable duct
  • Width IK 9271, SK 9271: 17.5 mm
    IL 9271, SL 9271, SL 9271CT: 35 mm
    IP 9271, SP 9271, SP 9271CT: 70 mm