Voltage and frequency monitor

RP 9812

Contacts

Auxiliary voltage

Supply voltage

Variant

  • 0070134
  • RP9812.03 3/N AC400/230V
The RP 9812 voltage and frequency monitor from the VARIMETER NA series is used to monitor the... more

Product description

The RP 9812 voltage and frequency monitor from the VARIMETER NA series is used to monitor the grid when feeding energy into the public grid. User-friendly: The unit can be adjusted quickly and simply with only three rotary switches. Use the first two rotary switches to select one of the preset standards according to the country-specific requirements. The third rotary switch is used to set the mains form quickly and easily on the device. You can adjust each parameter individually with menu-guidance in case of different requirements. All measuring variables required are constantly determined by the unit. If incorrect voltage or frequency values occur, the RP 9812 disconnects the distributed power generation System securely from the mains.

Technical specifications

Width: 70 mm
1- / 3-phase: 3
Supply voltage: 3/N AC 400/230 V
Auxiliary voltage: AC/DC
Operate delay: Yes
Output contacts: 3 NO contacts
Enclosure design: Distribution board
Type: RP 9812

Advantages

  • Mains and system protection for your generator set (NA protection)
  • Can be used in several countries
    - Generator sets on public grid according to VDE-AR-N 4105:2018-11
    - Generator sets on the medium voltage grid according to VDE-AR-N 4110:2023-09
    - Generator sets on the high voltage grid according to VDE-AR-N 4120:2018-11
  • Easy adjustment via rotational switch and menu display
  • Indication, diagnostics and fault presentation via display and LEDs
  • Password protected
  • Protection against manipulation by sealable transparent cover over setting switches
  • CRC-value for parameter testing
  • Adjustment of the voltage for nominal voltage will change the Limit values accordingly
  • Mains synchronization on generator operation
  • Fast switch-off on vector jump can be parameterized
  • RoCoF „Rate of Change of Frequency“ parameterized (Function df/dt)

Features

  • According to DIN EN 60255-1
  • Voltage and frequency monitoring for generator sets
  • Fail-safe 2-channel structure
  • Monitoring of the section switches by measuring the response time
  • System test via test button
  • Enabling inputs allow integration into various ripple control and plant concepts
  • Isolated grid detection
  • Manual reset
  • Memorising of disconnection time
  • Connection or re-connection after adjustable delay time tOn
  • Factory setting according to:
    VDE-AR-N 4105:2018-11, VDE-AR-N 4110:2023-09,
    VDE-AR-N 4120:2018-11
  • Random controlled disconnection in the range of 50.2 Hz and 51.5 Hz for non-regulated power generation systems
  • Random operated connection time (ton) setting range 60 ... 600 s
  • Additional fault signalling relay output
  • High measuring accuracy
  • Installion type enclosure 4TE (width x height x depth: 70 x 90 x 71 mm)