Description

The Phase monitor BD 9080 of the VARIMETER PRO series monitors over and undervoltage, asymmetry, power failure as well as wrong phase sequence at three-phase networks . The measurement is very simple and can be carried out without much wiring effort, as no separate auxiliary voltage is required. Early detection of impending failtures and preventive maintenance prevent costly damage and as a user you benefit from the operational safety and high availability of your system.

Technical specifications
1- / 3-phase: 3
Auxiliary voltage: Without
Enclosure design: Switch cabinet
Measuring range max.: 750 V
Operate delay: Yes
Output contacts: 2 C/O contacts
Standard measuring range: 3 AC 400 V
Type: BD 9080/004
Width: 45 mm
Features
  • According to IEC/EN 60255-1
  • Monitoring of
    - Under- and overvoltage up to 3 AC 1000 V max.
    - Asymmetry
    - Phase failure
    - Phase sequence
  • Adjustable on delay 0.1 ... 30 s
  • Without separate auxiliary voltage
  • Start up delay ta 30 s fixe
  • One LED in each case for
    - Operating voltage L1/L3
    - Overvoltage Umax.
    - Undervoltage Umin.
    - Asymmetry / Phase sequence / Power failure
    - Contact position
  • De-energized on trip
  • 2 changeover contacts
  • As option available with energized on trip