Skip to main content Skip to search Skip to main navigation
Menu
Description

The Over- and Undervoltage relays IL 9077/800 and SL 9077/800 of the VARIMETER PRO series monitor overvoltage, undervoltage and Phase failure in three-phase or single-phase networks. The measurement is simple and without extensive wiring, as no separate auxiliary supply is necessary. The early detection of up-coming break downs and preventive maintenance avoid expensive damages. As user you profit from the reliability and availability of your plant.

Technical specifications
1- / 3-phase: 1, 3
Auxiliary voltage: Without
Enclosure design: Distribution board
Measuring range max.: 400 V
Operate delay: Yes
Output contacts: 2 C/O contacts
Standard measuring range: 3/N AC 400/230 V
Type: IL 9077/800
Width: 35 mm
Advantages / Customer benefits
  • Preventive maintenance
  • For better productivity
Features
  • According to IEC/EN 60255-1
  • Identification of overvoltage, undervoltage and phase failure
  • Mains fault diagnostics with a number of LEDs
  • Setting values for overvoltage and undervoltage can be set separately
  • Large Setting Ranges 0.9 ... 1.3 UN and 0.7 ... 1.1 UN
  • Time delay on reset variable between 1 ... 60 s
  • De-energized on trip
  • No auxiliary voltage
  • Independant of phase sequence
  • Single-phase connection possible
  • Fast reaction on overvoltage
  • High overload possible
  • 2 changeover contacts
  • Devices available in 2 enclosure versions:
    IL 9077: Depth 59 mm, with terminals at the bottom for installation systems and industrial Distribution systems according to DIN 43880
    SL 9077: Depth 98 mm, with terminals at the top for Cabinets with mounting plate and cable duct
  • Width 35 mm