Skip to main content Skip to search Skip to main navigation
Menu
Description

Monitoring of 3-phase Motor systems with temperature sensing of the Motor thermistors, e.g. for elevators.

Technical specifications
1- / 3-phase: 3
Auxiliary voltage: Without
Enclosure design: Switch cabinet
Measuring range max.: 400 V
Output contacts: 2 x 1 C/O contacts
Standard measuring range: 3/N AC 400/230 V
Type: SL 9086
Width: 35 mm
Features
  • According to IEC/EN 60 255-1, IEC/EN 60 947-8 (pr EN 60 947-8) and part 303
  • Monitoring of
    - Undervoltage 3 phase
    - Phase failure
    - Phase sequence
    - Loss of neutral
    - Phase asymmetry
    - Overtemperature
    - Broken wire in thermistor circuit
    - Short circuit in thermistor circuit
  • Without auxiliary supply
  • 1 sensing input for 1 ... 6 thermistors
  • LED indication
    - Supply voltage
    - Measuring voltage
    - Temperature
  • As option with manual reset on temperature fault
  • 2 x 1 changeover contact
  • Devices available in 2 enclosure versions:
    IL 9086: depth 59 mm, with terminals at the bottom for installation systems and industrial distribution systems according to DIN 43 880
    SL 9086: depth 98 mm, with terminals at the top for cabinets with mounting plate and cable duct
  • Width 35 mm