Delay module, release delayed BG 7926

BG7926.png

Features

• According to
- Performance Level (PL) d and category 2 to EN ISO 13849-1: 2008
- SIL Claimed Level (SIL CL) 2 to IEC/EN 62061
- Safety Integrity Level (SIL) 2 to IEC/EN 61508 and IEC/EN 61511
when connected to a suitable safety module
• Redundant and forcibly guided contacts
• 1 timing circuit
• Fixed time delay 1, 2 or 3 sec
• Without auxiliary supply
• Output: 5 NO contacts or 4 NO contacts / 1 NC contact,
1 NC contact for feed back circuit
• Indicator LED for operation
• Removable terminal strips
• Wiring diameter: also 2 x 1.5 mm2 stranded ferruled with sleeve
DIN 46 228-1/-2/-3/-4 or 2 x 2.5 mm2 stranded ferruled
DIN 46 228-1/-2/-3
• Width 22.5 mm

• According to
- Performance Level (PL) d and category 2 to EN ISO 13849-1: 2008
- SIL Claimed Level (SIL CL) 2 to IEC/EN 62061
- Safety Integrity Level (SIL) 2 to IEC/EN 61508 and IEC/EN 61511
when connected to a suitable safety module
•...

more...
Function Delay module, release delayed
Cat. / PL according to EN ISO 13849-1 2/d
SIL CL according to IEC/EN 62061 2
1- / 2-channel 1
Output contacts max. 5 s; 1 ö
Thermal current Ith max. 5 A
Nominal voltage AC/DC +
Time delay max. 3 sec
Approvals UL-Recognized
Connection PS
Width 22,5 mm
Type BG 7926

Please select required language:

Datasheet / Operating Instructions, File: pdf, File size 218 KB

 

 

Your contact


    Competence on site

    Damit wir für Sie Ihren persönlichen Ansprechpartner finden können, geben Sie bitte die fünfstellige Postleitzahl Ihres Ortes in das Suchfeld ein.

    Contact for: