XF 6929

Extension module

XF 6929

Contacts

Nominal voltage

Variant

  • 0069254
  • XF6929.23 DC24V
If more safety circuits are required than provided by a safety module, the extension module XF... more

Product description

If more safety circuits are required than provided by a safety module, the extension module XF 6929 from the SAFEMASTER series is used. With its forcibly guided contacts it can be used to safely connect control and load circuits as well as to multiply the number of safety contacts and for contact reinforcement of safety modules and PLCs with monitoring of the feed back circuit. Safe semiconductor outputs can be turned into volt free contacts using XF 6929.

Technical specifications

Width: 17,5 mm
Cat. / PL acc. to EN ISO 13849-1: 4/e
SIL acc. to IEC/EN 62061: 3
Nominal voltage: DC
Thermal current Ith max.: 8 A
1- / 2-channel: 1, 2
Connection: Front side cage clamp terminals
Output contacts max.: 6 NO contacts, 2 NC contacts
Type: XF 6929

Advantages

  • Safe contact multiplication
  • Cost and space saving alternative compared to contactors
  • Reinforced insulation acc. to IEC 60664-1 and IEC 61010-1-1

Features

  • Can be used in conjunction with a suitable switchgear / control unit in safety applications as follows:
    - Up to PL e and category 4 according to EN ISO 13849-1
    - Up to maximum SIL 3 according to EN IEC 62061
    - Up to SIL 3 according to EN 61508 and EN 61511
  • According to EN 50156-1 for furnaces
  • Control from semiconductor safety outputs (light curtains, e-stop, etc.) is also possible
  • Redundant and forcibly guided contacts
  • For 1- or 2-channel circuits
  • Indication for operating condition
  • Width: 17.5 mm