• According to
- Performance Level (PL) e and category 4 to EN ISO 13849-1
- SIL Claimed Level (SIL CL) 3 to IEC/EN 62061
- Safety Integrity Level (SIL) 3 to IEC/EN 61508 and IEC/EN 61511
• Acc. to EN 50156-1 for furnaces
• Line fault detection on On-button:
• Manual restart or automatic restart
• With or without cross fault monitoring
• 2-channel
• Forcibly guided output contacts
• Output: 2 NO instantaneous contact and 2 NO contacts delayed
• 1 semiconductor output for instantaneous contacts
1 semiconductor output for delayed contacts
• LED indicator for operation, safety function, time delay and failure
• As option with pluggable terminal blocks for easy exchange of devices
- with screw terminals
- or with cage clamp terminals
• Width: 22.5 mm
• According to
- Performance Level (PL) e and category 4 to EN ISO 13849-1
- SIL Claimed Level (SIL CL) 3 to IEC/EN 62061
- Safety Integrity Level (SIL) 3 to IEC/EN 61508 and IEC/EN 61511
• Acc. to EN 50156-1 for furnaces
• Line fault...
• Various delay functions adjustable at device:
- Release delay
- Release delay retriggerable
- On delay
- Fleeting on make / break
- Delay function settable via potentiometer
• Various safety functions defined:
- E-Stop
- Safety gate
- Two-hand control
- Safety mat / Safety edge
- Exclusive or contacts
- Light curtain
• Manual or auto start
• Instantaneous contact and safety delayed contacts
• Protection against manipulation by sealable transparent cover
• Various delay functions adjustable at device:
- Release delay
- Release delay retriggerable
- On delay
- Fleeting on make / break
- Delay function settable via potentiometer
• Various safety functions defined:
- E-Stop
- Safety gate
- Two-hand...
Function | Multifunctional safety timer with instantaneous contacts |
Application emergency stop | + |
Application light barrier | + |
Application safety gate | + |
Application two-hand | + |
Application safety mat | + |
Cat. / PL according to EN ISO 13849-1 | 4/e |
SIL CL according to IEC/EN 62061 | 3 |
1- / 2-channel | 2 |
Safe output contacts, redundant NO contacts max. | 4 |
Thermal current Ith max. | 8 A |
Nominal voltage DC | + |
Cross fault detection | + |
Approvals | UL |
Connection | PS/PC/PT |
Width | 22,5 mm |
Type | UG 6960 |
Please select required language:
Datasheet / Operating Instructions, File: pdf, File size 1 MB
Flyer, Multifunctional safety module UG 6970, File: pdf, File size 237 KB
Flyer, Multifunctional safety timer UG 6960, File: pdf, File size 237 KB
Brochure, Product overview SAFEMASTER C, File: pdf, File size 430 KB
Brochure, Product overview SAFEMASTER, File: pdf, File size 1 MB
EPLAN Electric P8 Makro, UG 6960, File: zip, File size 5 MB
The multifunction safety timer UG 6960 provides protection of men and machines by enabling and disabling a safety circuit. This is done by the adjusted time delay function. Simply select 1 out of 5 delay functions with a rotary switch – ready. The adjusted time is safe over the complete setting range. The UG 6960 is available for different safety functions. It has safe delayed and instantaneous contacts.