Emergency stop module
LG 5925
- Protection of people and machines
- Emergency stop circuits on machines
- Monitoring of safety gates
- Usage in furnace application in continuous operation acc. to EN 50156-1
- Safe disconnection of the complete fuel supply in furnace
applications according to EN 50156-1 section 10.5.5.2
| 1- / 2-channel: | 1, 2 |
|---|---|
| Approvals: | UL |
| Cat. / PL acc. to EN ISO 13849-1: | 4/e |
| Connection: | Pluggable cage clamp terminals, Pluggable screw terminals, Screw terminals |
| Cross fault detection: | Yes |
| Nominal voltage: | AC, AC/DC |
| Output contacts max.: | 4 NO contacts |
| SIL acc. to IEC/EN 62061: | 3 |
| Suited as safety gate monitor: | Yes |
| Thermal current Ith max.: | 8 A |
| Width: | 22,5 mm |
| Type: | LG 5925 |
- According to
- Performance Level (PL) e and category 4 to EN ISO 13849-1
- SIL Claimed Level (SIL CL) 3 to IEC/EN 62061
- Safety Integrity Level (SIL) 3 to IEC/EN 61508 and IEC/EN 61511 - According to EN 50156-2 for furnaces
- Output: max. 4 NO contacts, see contacts
- LG 5925.54: 1 semiconductor output
- Single and 2-channel operation
- Line fault detection on On-button
- Manual restart or automatic restart, switch S2
- With or without cross fault monitoring in the E-stop loop, switch S1
- LG 5925.54: with cross fault monitoring in the E-stop loop
- LED indicator for channel 1, 2 and supply voltage
- Removable terminal strips
- Wire connection: also 2 x 1.5 mm2 stranded ferruled, or 2 x 2.5 mm2 solid DIN 46228-1/-2/-3/-4
- As option with pluggable terminal blocks for easy exchange of devices
- With screw terminals
- Or with cage clamp terminals - Width: 22.5 mm