Emergency stop module with time delay LG 5928

LG5928.png

Features

• According to
- Performance Level (PL) e and category 4 to EN ISO 13849-1: 2008
- SIL Claimed Level (SIL CL) 3 to IEC/EN 62061
- Safety Integrity Level (SIL) 3 to IEC/EN 61508 and IEC/EN 61511
• Output: 2 NO instantaneous contacts and 1 release delay contact
• 1- or 2-channel connection
• Line fault detection at the ON pushbuttons at connection on
terminals S33-S34
• Manual restart with button on S33-S34 or automatic restart with
bridge between S13-S34
• With or without cross fault monitoring in the E-stop loop
• Indication for released time circuit
• LED indication for supply, channel 1/2 and release delayed contacts
• Wire connection: also 2 x 1.5 mm2 stranded ferruled (isolated),
DIN 46 228-1/-2/-3/-4 or 2 x 2.5 mm2 stranded ferruled DIN 46 228-1/-2/-3
• As option with pluggable terminal blocks for easy exchange of devices
- with screw terminals
- or with cage clamp terminals
• Width 22.5 mm

• According to
- Performance Level (PL) e and category 4 to EN ISO 13849-1: 2008
- SIL Claimed Level (SIL CL) 3 to IEC/EN 62061
- Safety Integrity Level (SIL) 3 to IEC/EN 61508 and IEC/EN 61511
• Output: 2 NO instantaneous contacts and 1...

more...

Advantages / Customer benefit

• Compact, flexible and safe
• Short response time
• Ideal for designs according to the new safety standards

Function Emergency stop module with time delay
Also suited as safety gate monitor +
Cat. / PL according to EN ISO 13849-1 4/e
SIL CL according to IEC/EN 62061 3
1- / 2-channel 1; 2
Output contacts max. 2 s; 1 sv
Thermal current Ith max. 8 A
Cross fault detection +
Nominal voltage DC +
Approvals UL
Connection S/PS/PC
Width 22,5 mm
Type LG 5928