Dold Industries Ltd

11 Hamberts Rd. Blackall Ind. Estate
South Woodham Ferrers
GB-Essex, CM3 5UW
BH 5928

Emergency stop module with time delay

BH 5928

Contacts

Nominal voltage

Time range

Approvals and Markings

Variant

  • 0049014
  • BH5928.93/61 DC24V 1-10S
Protection of people and machines Emergency stop circuits on machines, stop category 1 can... more

Product description

  • Protection of people and machines
  • Emergency stop circuits on machines, stop category 1 can be realised
  • Monitoring of safety gates

Technical specifications

Width: 45 mm
Cat. / PL acc. to EN ISO 13849-1: 4/e
SIL CL acc. to IEC/EN 62061: 3
Nominal voltage: DC, AC/DC
Suited as safety gate monitor: Yes
Thermal current Ith max.: 5 A
1- / 2-channel: 1, 2
Cross fault detection: Yes
Connection: Pluggable screw terminals
Output contacts max.: 3 NO contacts, 3 NO contacts delayed
Approvals: UL
Type: BH 5928

Features

  • According to
    - Performance Level (PL) e and category 4 to EN ISO 13849-1
    - SIL Claimed Level (SIL CL) 3 to IEC/EN 62061
    - Safety Integrity Level (SIL 3) to IEC/EN 61508 and IEC/EN 61511
  • Output: 3 NO or 2 NO, 1 NC instantaneous contacts and 3 NO release delayed contacts
  • Single and 2-channel operation
  • Line fault detection on On-button, when On-button is connected to S33-S34
  • Manual restart with button on S33-S34 or automatic restart with bridge between S13-S14
  • With or without cross fault monitoring in the E-stop loop
  • LED indication for supply, channel 1/2 and release delayed contacts
  • Removable terminal strips
  • Wire connection: also 2 x 1.5 mm2 stranded ferruled (isolated), DIN 46 228-1/-2/-3/-4 or 2 x 2.5 mm2 stranded ferruled DIN 46 228-1/-2/-3
  • Width
    BH 5928: 45 mm
    BI 5928: 67.5 mm