Dold Industries Ltd

11 Hamberts Rd. Blackall Ind. Estate
South Woodham Ferrers
GB-Essex, CM3 5UW
IP 5880/711

Insulation monitor

IP 5880/711

Contacts

Auxiliary voltage

Alarm value

Approvals and Markings

Variant

  • 0057875
  • IP5880.12/711 AC50-400HZ 220-240V
For insulation monitoring of the IT system of rooms used for medical purposes according to VDE... more

Product description

For insulation monitoring of the IT system of rooms used for medical purposes according to VDE 0100-710.

Technical specifications

Width: 70 mm
Classification: For medically used rooms
Response value: 50 - 500 kΩ
IMD type: AC
Nominal voltage IT system: AC 0 - 500 V
Auxiliary voltage: AC
Earth fault indicator: Yes
Response value type: Adjustable
Enclosure design: Distribution board
Type: IP 5880/711

Features

  • According to IEC/EN 61 557-8
  • For rooms used for medical purposes
    according to IEC 60364-7-710, DIN VDE 0100-710
  • For three-phase and A.C. power systems with 0 … 500 V 
    and 10 … 1000 Hz (IT power systems)
  • Adjustable alarm value for ground fault RAL of 50 … 500 kΩ
  • Measuring circuit with broken wire protection
  • As option, programmable for storing or non-storing of errors
  • With reset and test button
  • Additional external reset and test buttons can be connected
  • LED indicators for operation, insulation fault, and interruption of Measuring circuit
  • 2 changeover contacts
  • With LED chain for indication of the current insulation status
  • IP 5880/711 for connection of the test and display panel UP 5862
  • 52.5 mm width