Insulation monitor
LK 5896/900
- Article number: 0066991
- Type: LK5896.13/900/61 DC24V 1k-250k
Product description
The insulation monitor LK 5896/900 of the VARIMETER IMD family is a solution for optimal insulation monitoring of modern IT systems. The device can be used in the most flexible way for AC, DC and AC/DC systems even with large leakage capacity to earth (PE). By using a trigger input and a trigger output 2 separate IT systems can be coupled and monitored during operation without the problem that the 2 insulation monitors disturb each other. The adjustment of the setting values is simple and user friendly done on 2 rotary switches on the front of the device. Via LEDs the measured value, device parameters and device status are indicated easy to read. The unit has 3 relay contacts to signal Insulation and device failures. The analogue output provides a voltage and current signal proportional to the actual insulation resistance, which can be connected to a superior control (plc), another system or external display unit.
Technical specifications
Width: | 90 mm |
Response value: | 1 - 250 kΩ |
IMD type: | AC, DC, AC/DC |
Nominal voltage IT system: | AC 0 - 1000, DC 0 - 1000 V |
Auxiliary voltage: | DC |
Earth fault indicator: | Yes |
Approvals: | UL |
Connection for indicator: | Yes |
Response value type: | Adjustable |
Enclosure design: | Switch cabinet |
Type: | LK 5896/900 |
Downloads
Advantages
- Preventive fire and system protection
- System for sequential monitoring of separated voltage systems, that can be coupled
- Quick fault localisation through selective earth fault detection to L+ and L-
- Universal application in non-earthed AC, DC, AC/DC networks with up to 1000 V nominal voltage
- Suitable for large leakage capacitances up to 3000 μF
- Simplest setting via engaging rotary switches
- Optimised measuring times - normally shorter than with known methods
- Monitoring also with voltage-free mains
- Measuring circuit with broken wire detection
- No additional coupling device required
- Analogue output for value of the insulation resistance: 0 ... 10 V / 0 ... 20 mA (2 ... 10 V / 4 ... 20 mA)
Features
- Insulation monitoring according to IEC/EN 61557-8
- Detection of symmetric and asymmetric insulation faults
- 1 changeover contact each for prewarning and alarm
- 3. output relay for signalling wire break and device faults
- Prewarning threshold setting range: 20 kΩ ... 2 MΩ
- Alarm threshold setting range: 1 kΩ ... 250 kΩ
- Energized or de-energized on trip can be selected for output relay
- Setting the maximum leakage capacitance to shorten the response time
- Simple, clearly arranged adjustment of the device with screwdriver
- LED chain to indicate the current insulation resistance
- Display " measuring circuits active"
- Display "Master" or "Slave"
- Automatic and manual device self-test
- Alarm storage selectable
- External test and reset pushbutton can be connected
- With watchdog timer to monitor the trigger signal
- Width: 90 mm