Dold Industries Ltd

11 Hamberts Rd. Blackall Ind. Estate
South Woodham Ferrers
GB-Essex, CM3 5UW
BD 5936

Standstill Monitor

BD 5936

Contacts

Auxiliary voltage

Approvals and Markings

Variant

  • 0046456
  • BD5936.17 AC50/60HZ 230V
The BD 5936 detecting standstills of 3- and 1-phase asynchronous motors. At 2 terminals of the... more

Product description

The BD 5936 detecting standstills of 3- and 1-phase asynchronous motors. At 2 terminals of the stator winding the BD 5936 measures the voltage of the slowing motor which has been induced. If the induction voltage approaches 0 this indicates that the device is at a standstill and the output relay is activated. Additional the monitor detects strand breaks between measurement inputs Z1 / Z2. If a line breakage is detected, the output relay goes into the normal position (as when the motor is running). This state is saved and can only be cleared by (briefly) switching off the auxiliary voltage.

Technical specifications

Width: 45 mm
Auxiliary voltage: AC, AC/DC
Classification: Stillstandsüberwachung
Output contacts: 2 NO contacts, 2 NC contacts
Enclosure design: Switch cabinet
Type: BD 5936

Advantages

  • Standstill monitoring without sensor

Features

  • According to IEC/EN 60255-1, IEC/EN 60255-26
  • For standstill monitoring of 3- and 1-phase asynchronous motors
  • Line breakage detection in the measurement circuit
  • Forcibly guided output contacts:
    2 NO, 2 NC contacts for 250 V AC
  • LED indicators for motor standstill, line breakage and
    operating voltage
  • Wire connection: also 2 x 1.5 mm2 stranded ferruled (isolated),
    DIN 46 228/-1/-2/-3/-4 or
    2 x 2.5 mm2 stranded ferruled DIN 46 228-1/-2/-3
  • Width 45 mm