Dold Industries Ltd

11 Hamberts Rd. Blackall Ind. Estate
South Woodham Ferrers
GB-Essex, CM3 5UW
IR 5882

Residual current monitor, Type A, with integrated transformer

IR 5882

Contacts

Auxiliary voltage

Measuring range

Time delay

Approvals and Markings

Variant

  • 0066143
  • IR5882.38 AC/DC24-230V 10A tv=5S
The residual current monitor IR 5882 of the VARIMETER RCM series is used for early detection of... more

Product description

The residual current monitor IR 5882 of the VARIMETER RCM series is used for early detection of insulation faults and detects residual currents with alternating currents and pulsating direct currents in earthed systems (type A). The residual current measurement is carried out via an integrated current transformer. In contrast to the residual current circuit breaker, the residual current monitor IR 5882 does not immediately switch off the mains when a fault is detected, but only indicates the fault. LEDs indicate operational readiness, pre-alarm and alarm. Other features include a check and delete function. The IR 5882 residual current monitor thus offers an information advantage for targeted and cost-effective maintenance measures before the system comes to a standstill.

Technical specifications

Width: 105 mm
Adjustable measuring ranges: 0,01 - 10 A
Operate delay: Yes
Classification: Type A (AC, DC pulsating)
Type of voltage: AC, DC pulsating
Broken conductor detection: Yes
Clear key: Yes
Test key: Yes
Relay contact / output: Yes
Enclosure design: Distribution board
Type: IR 5882

Advantages

  • Preventive fire and system protection
  • Increasing the availability of plants by early fault detection
  • With internal residual current transformer
  • Protection against manipulation by sealable transparent cover over setting switches

Features

  • According to IEC/EN 62020
  • For AC and pulsating DC currants Type A to IEC/TR 60755
  • 9 tripping values from 10 mA to 10 A or from 10 mA ... 30 A
  • Frequency range 20 ... 2000 Hz
  • Selection of manual or automatic reset
  • With prewarning
  • With test and reset button
  • Short reaction time
  • With adjustable delay tv
  • De-energized on trip
  • LED indication for auxiliary supply and state of contact
  • 2 x 1 changeover contact
  • 63 mm deep with terminals near to the bottom to be mounted in consumer units or industrial distribution systems according to DIN 43880
    - Width 105 mm
    - With internal residual current transformer